Self-Regulating Heating Cable

SLCBL Self-Regulating Heating Cable
 
Product highlights:
  • Ideal for freeze protection and low temperature process maintenance up to 65°C
  • Automatically adjusts heat output based on surface temperature
  • Safe to overlap and insulate
  • Can be cut-to-length and terminated in the field
Specifications:
  • Maximum continuous maintenance temperature: 65°C
  • Maximum intermittent exposure temperature: 85°C
  • Minimum intermittent exposure temperature: -40°C
  • Nominal power output at 10°C: 10, 17, 25, 31, 40 W/m
  • Supply voltages (AC): 110-120V or 208-277V
  • Moisture, chemical and flame resistant
  • Bus wire gauge: 16 AWG
  • Braid resistance: Tinned copper 0.0182 ohms/m
  • T6 Rating - 10, 17, 25, 31 W/m
  • T5 Rating - 40 W/m